GENERAL NOTE : A - TRIPS RELATED TO SUBSEA WELLS SHALL BE ANALYZED AND ADDED TO THE ESD LOGIC DIAGRAMS
XS-19716
XS-19756
FIRE IN SHELTER
02
DURING PHASE 2. ESD-1.7 / GAS NOTES : 249008
1 - DELETED.
BY PASS OF AHU HEATING COIL
STOP THE DUTY FAN AND SWITCH TO THE STAND-BY FAN
NOTE 2
2 - HVAC CONTROL PANEL SHALL DISPLAY AN ALARM TO THE SAFETY SYSTEM. 3 - ONLY WHEN RIG IS AT STATION.
HOLDS :
4 - TIME DELAY ADJUSTABLE.
1 - DELETED.
6 - VOTING LOGIC IS 2oo2 BY LOOPS. TWO SYMMETRICAL LOOPS, EACH CONTAINING OPTICAL SMOKE
4 - DELETED.
-
-
-
249007
-
-
-
-
-
-
-
-
02
12-Sep-2017
AFD
ACCEPTED FOR DESIGN
01
10-Jul-2017
IFA
ISSUED FOR ACCEPTANCE
00
23-May-2017
IFR
ISSUED FOR REVIEW
Rev.
Date
Status
02
Affiliate:
DETECTORS AND HEAT DETECTORS, TO TRIGGER ESD-1.
ARGENTINA
Check. Appr.
Site:
FEN
Project Phase: BE
LEGEND :
CONTROL AND STATUS PANEL, TO CONFIRM CO 2 RELEASE IN THE PROTECTED SPACE VIA
ESD 1.2/1.3/1.4/FIRE
PLATFORM FGS. ALARM TO BE SHOWN ON TR AND RCCR HMI.
SHUTDOWN LEVEL WITH MANUAL RESET
8 - LOCAL ALARM AT SHELTER ENTRANCE AND AT GENERATOR ENCLOSURES ENTRANCE.
DESCRIPTIONS OF MAC.
Iss.
EMERGENCY SHUTDOWN DIAGRAM
7 - PAH ON CO 2 SYSTEM DISCHARGE LINE TO SWITCH ON DEDICATED LIGHT ON THE CO 2 LOCAL
9 - REFER TO AR-FEN-10-DOEC-376002 " INSTRUMENT AND INPUT / OUTPUT LIST " FOR TAGS AND
Revision Description
This document is the property of the TOTAL GROUP and it shall not be disclosed to third parties or reproduced without the express written permission of the TOTAL GROUP. This document has been generated by an Electronic Document Management System. When printed it shall be considered as "for information only". The controlled copy is the EDMS version and it is document holder's responsibility to make sure that latest version is in use.
3 - DELETED.
VOLUME OF THE ROOM AND IN THE FALSE FLOOR.
-
HVAC CONTROL PANEL (19-BHV-001)
2 - DELETED.
5 - VOTING LOGIC IS 2oo3 BY LOOPS. EACH LOOP CONTAINS OPTICAL SMOKE DETECTORS IN THE