RIG

02

NOTE 3

2ooN

2ooN

ESDV / DRAIN DECK ESD-1.2/FIRE

MEZZANINE DECK

GEG UCP

FIRE IN OPEN AREA

2ooN

LOWER DECK SDG UCP

GAS ENGINE GENERATOR 19-X-3400

STANDBY DIESEL GENERATOR 19-X-3410

ESD-1

02

249007 SD HVAC PACKAGE GAS CONFIRMED IN GEG ENCLOSURE

2oo3

2oo3

2oo3

249008

2oo3

02

CO2 RELEASE

02

SHUTDOWN OF VENTILATION AND CLOSURE OF FIRE DAMPERS

CO2 SIREN & BEACONS

02

UXS-19755

NOTE 4

UXS-19757

Td 10s

HS AUTO

CO2 RELEASED IN GEG ENCLOSURE

&

PB CO2

&

Td 10s CO2 RELEASE

NOTE 4

02

CO2 SIREN & BEACONS

ESD-1.1/GAS

CO2 RELEASED IN SDG ENCLOSURE

249008

ESD-1.2.1/FIRE

SHUTDOWN OF VENTILATION AND CLOSURE OF FIRE DAMPERS

NOTE 7

PAH-19762 S

PB CO2

&

PAH-19749-N

&

UXS-19744 UXS-19742

GSHH-19715

HS AUTO

UXS-19766

2oo3 25% LEL

XV-19623 DELUGE

UXS-19769

3-WAY VALVE

UXS-19767

3-WAY VALVE

XS-19652S STOP/INHIBIT STANDBY DIESEL GENERATOR 19-X-3410

NOTE 7

ESD-1.3/FIRE FIRE IN GENERATORS SD-3.4

WAVE OFF

249013

ALARM

ACCOMMODATION SD-3.6

249013

249013

BEDROOM 1

BEDROOM 2

ESD-1 KITCHEN + DINING ROOM

249007

WORKSHOP

TECHNICAL ROOM

HS AUTO

3 WAY VALVE

SD-3.4

LOOP 1

OR

LOOP 1

LOOP 2

LOOP 3 2oo3 NOTE 5

DOOR OPEN

&

ACTIVATE ALARM NOTE 8

02

3-WAY VALVE

AHU AIR INTAKE

2oo2

AHU OUTLET FAN "A" OUTLET FAN "B" OUTLET

NOTE 6

02

&

Td 30s

HVAC PACKAGE

PB CO2 &

02

NOTE 4

CO2 RELEASE

CO2 SIREN & BEACONS

CO2 RELEASED IN TECHNICAL ROOM

NOTE 9

02

2oo3

UXS-19768

HS AUTO

LOOP 2

2oo3

GPA UXH19717

02

NOTE 7 ESD-1.4/FIRE

GENERAL NOTE : A - TRIPS RELATED TO SUBSEA WELLS SHALL BE ANALYZED AND ADDED TO THE ESD LOGIC DIAGRAMS

XS-19716

XS-19756

FIRE IN SHELTER

02

DURING PHASE 2. ESD-1.7 / GAS NOTES : 249008

1 - DELETED.

BY PASS OF AHU HEATING COIL

STOP THE DUTY FAN AND SWITCH TO THE STAND-BY FAN

NOTE 2

2 - HVAC CONTROL PANEL SHALL DISPLAY AN ALARM TO THE SAFETY SYSTEM. 3 - ONLY WHEN RIG IS AT STATION.

HOLDS :

4 - TIME DELAY ADJUSTABLE.

1 - DELETED.

6 - VOTING LOGIC IS 2oo2 BY LOOPS. TWO SYMMETRICAL LOOPS, EACH CONTAINING OPTICAL SMOKE

4 - DELETED.

-

-

-

249007

-

-

-

-

-

-

-

-

02

12-Sep-2017

AFD

ACCEPTED FOR DESIGN

01

10-Jul-2017

IFA

ISSUED FOR ACCEPTANCE

00

23-May-2017

IFR

ISSUED FOR REVIEW

Rev.

Date

Status

02

Affiliate:

DETECTORS AND HEAT DETECTORS, TO TRIGGER ESD-1.

ARGENTINA

Check. Appr.

Site:

FEN

Project Phase: BE

LEGEND :

CONTROL AND STATUS PANEL, TO CONFIRM CO 2 RELEASE IN THE PROTECTED SPACE VIA

ESD 1.2/1.3/1.4/FIRE

PLATFORM FGS. ALARM TO BE SHOWN ON TR AND RCCR HMI.

SHUTDOWN LEVEL WITH MANUAL RESET

8 - LOCAL ALARM AT SHELTER ENTRANCE AND AT GENERATOR ENCLOSURES ENTRANCE.

DESCRIPTIONS OF MAC.

Iss.

EMERGENCY SHUTDOWN DIAGRAM

7 - PAH ON CO 2 SYSTEM DISCHARGE LINE TO SWITCH ON DEDICATED LIGHT ON THE CO 2 LOCAL

9 - REFER TO AR-FEN-10-DOEC-376002 " INSTRUMENT AND INPUT / OUTPUT LIST " FOR TAGS AND

Revision Description

This document is the property of the TOTAL GROUP and it shall not be disclosed to third parties or reproduced without the express written permission of the TOTAL GROUP. This document has been generated by an Electronic Document Management System. When printed it shall be considered as "for information only". The controlled copy is the EDMS version and it is document holder's responsibility to make sure that latest version is in use.

3 - DELETED.

VOLUME OF THE ROOM AND IN THE FALSE FLOOR.

-

HVAC CONTROL PANEL (19-BHV-001)

2 - DELETED.

5 - VOTING LOGIC IS 2oo3 BY LOOPS. EACH LOOP CONTAINS OPTICAL SMOKE DETECTORS IN THE

ESD-1

. Discipline:

02

SHUTDOWN LEVEL WITH AUTOMATIC RESET

Doc. Type:

PRO

Company Doc. N°:

ESD

Sector:

AR-FEN-10-DOEC-249009

Contractor Doc. N°: -

19

Class: Format:

System:

03

1

Scale:

N/A

A1

Folio:

1 of 1
AR-FEN-10-DOEC-249009_rev02 - Emergency Shutdown Diagram ESD 1.2_1.3_1.4_Fire